Products  /  NTP Time Servers  /  ORNATE 7000 TSDRNT

Overview

Stratum 1 Time for Every Network on Site

The ORNATE 7000 TSDRNT is a Stratum 1 network time reference for power, process, IT, telecom and railway installations. It takes time from GNSS satellites (GPS, NavIC, Galileo, BeiDou and GLONASS) and distributes it over three independent NTP/SNTP ports, a dedicated PTP (IEEE 1588) grandmaster port, 1PPS, RS-232, RS-485 and four programmable potential-free contacts.

Each NTP port has its own IP address, so one unit can serve three separate networks — for example SCADA, office LAN and CCTV — with no routing between them. A 16 × 2 backlit LCD shows date, time and synchronisation status at a glance, and a GPS-fail alarm contact reports loss of reference.

Key Features

One Time Source, Every Network

🔀

Three NTP Ports + PTP Grandmaster

Three independent NTP/SNTP Ethernet ports (NTP v3/v4, RFC 5905), served in parallel, each with its own IP, mask and gateway — for Windows and Linux servers, IEDs, PLCs, NVRs and switches. A fourth, dedicated PTP port acts as an IEEE 1588 grandmaster with hardware time-stamping.

🛰️

Dual-Band, Multi-Constellation GNSS

L1 + L5 reception from GPS, NavIC, Galileo, BeiDou, GLONASS and QZSS, with a GNSS receiver timing accuracy of 5 ns (1σ, receiver specification). If GNSS is lost, the server keeps time for a settable holdover period of 1 minute to 24 hours — see our GNSS resilience guide.

⚡

Power-Utility PTP Profiles

IEEE 1588-2008 (PTPv2) with the IEC/IEEE 61850-9-3 power utility and IEEE C37.238-2017 power profiles, plus default E2E and P2P. Layer 2 or UDP/IPv4, multicast and unicast (up to 32 slaves) — for substation automation and numerical relays.

🔌

Serial, 1PPS & Contact Outputs

  • 1PPS, TTL level on BNC
  • RS-232 and isolated RS-485: NMEA ZDA, NGTS, T-Format
  • 4 programmable potential-free contacts: PPS, PP5S, PPM, PPQH, PPHH, PPH, PPD
  • Fail-safe GPS-fail alarm contact
🔒

Secure by Design

Password-protected web configuration with login lock-out and session time-out. Management commands are signed with HMAC-SHA256, so the password never travels on the network, and NTP control/monitor queries are disabled. It never serves untraceable time: outputs are held when the unit is not synchronised.

🗄️

Easy Setup & Central Management

Configure from any web browser, or manage every unit from our Management Server Software → — live status, history, events and settings. Alarms and events go to two SYSLOG servers.

Applications

Where the TSDRNT Is Used

🏭

Power & Process

Substation automation (IEC 61850) and numerical relays; event loggers and disturbance recorders; SCADA, DCS and EMS servers.

🚆

Telecom, Railway & Control Rooms

Telecom, railway and control-room networks, and slave display clocks (wired and RF).

🖥️

IT & Security

Data centres, CCTV / NVR and IT servers — see NTP for data centres.

Specifications

Technical Specifications

GNSS Receiver
ConstellationsGPS, NavIC (IRNSS), Galileo, BeiDou, GLONASS, QZSS
Frequency bandsL1 / E1 / B1 and L5 / E5a / B2a (dual-band)
Channels184
Receiver timing accuracy5 ns (1σ), GNSS receiver specification
Time referenceUTC from GNSS, disciplined system clock (1PPS-locked)
HoldoverKeeps serving time after loss of GNSS for a settable period (1 min – 24 h, default 4 h), then reports “not synchronised”
Antenna
TypeActive multi-band GNSS timing antenna, outdoor
Antenna cableRG-6, 50 m standard (other lengths on request)
ProtectionWeather-proof radome; lightning arrester supplied
MountingPole / wall mount with fixing accessories
NTP Ports (LAN)
Ports3 × RJ45, 10/100 Mbps, auto-negotiation
AddressingIndependent static IP, mask and gateway per port
ProtocolNTP v3 / v4 (RFC 5905), SNTP; UDP / IPv4
ModeServer (unicast client / server)
Stratum1 when synchronised; 16 with alarm flag (LI = 3) when not
PTP Port
Port1 × RJ45, 10/100 Mbps, hardware time-stamping
StandardIEEE 1588-2008 (PTPv2), grandmaster, two-step
ProfilesDefault E2E and P2P; IEC/IEEE 61850-9-3 (power utility); IEEE C37.238-2017 (power, with TLV); custom
TransportEthernet Layer 2 or UDP / IPv4 (own IP)
Delay mechanismEnd-to-end (E2E) or peer-to-peer (P2P)
MessagingMulticast, unicast (negotiated, up to 32 slaves) or both; hybrid unicast Delay_Resp
Message ratesSync up to 16 / s; Announce up to 8 / s
Domain / priorityDomain 0 – 127 or 254; Priority 1 / 2 settable
Time-scalePTP (TAI) with UTC offset and leap flags from GNSS, or ARB
Best masterSteps aside automatically if a better grandmaster appears
Time Signal Outputs
1PPS output1 pulse per second, rising edge on time; TTL level (5 V open circuit, ≈ 2.5 V into 50 Ω); BNC; 100 ms pulse width; suppressed when not synchronised
Serial outputs1 × RS-232 (DB9) and 1 × isolated RS-485; NMEA ZDA, NGTS, T-Format (selectable per port); 1200 – 115200 baud, 8-N-1
Potential-free contacts4 × programmable, solid-state, normally open; modes PPS, PP5S, PPM, PPQH, PPHH, PPH, PPD (time of day settable); pulse width 10 ms – 10 s; UTC or IST time base; normal or inverted; 125 V DC / 88 V AC rms, 75 mA
Alarm contact1 × GPS-fail potential-free changeover contact (NO / COM / NC), 30 V DC, 1 A (SELV); fail-safe — drops out on fault or power loss; optional alarm while in holdover
Display, Indication & Configuration
Display2 × 16 character backlit LCD
Status LEDsPower, System OK; link / activity on every Ethernet port
Displayed dataDate and UTC time; synchronisation state, GNSS and 1PPS status; port IP address and NTP request count; unit ID
ConfigurationWeb browser (HTTP), password protected; BiharCom Management Server software (Windows)
Settings storageNon-volatile memory; restore defaults from the management software
Network Protocols & Management
Time protocolsNTP v3 / v4 (RFC 5905) server, SNTP clients; PTPv2 – IEEE 1588-2008 grandmaster (multi-profile)
NetworkingIPv4, UDP, TCP, ARP, ICMP (ping), IGMPv2 (PTP port)
SYSLOGRFC 5424, two configurable servers; selectable facility, severity and event groups (sync, GNSS, alarm, network, PTP, outputs, system, configuration, security)
Central managementAuto-discovery of units, live status, clock history, event log, remote configuration, save and reboot
Network Security
Web accessUser name and password; 5 failed logins lock access for 60 s; 15 min session time-out
Management commandsHMAC-SHA256 signed with one-time challenge (replay-protected); password never sent over the network
NTP hardeningControl (mode 6) and private (mode 7) queries disabled — no amplification risk
AuditLogins, failures and configuration changes reported to SYSLOG
Synchronisation Integrity
Not synchronisedNTP stratum 16 with alarm flag; PTP clock class “not traceable”; 1PPS and serial time withheld
HoldoverKeeps serving time for the set holdover period; optional alarm while in holdover
Self-recoveryWatchdog supervision; a stalled network port is reset on its own without disturbing the others
Status reportingLCD, alarm contact, web page, management software and SYSLOG
Power, Environment & Mechanical
Power input90 – 264 V AC, 47 – 63 Hz / 127 – 370 V DC
Consumption< 15 W
Operating temperature0 to +50 °C
Storage temperature−20 to +70 °C
HumidityUp to 90 % RH, non-condensing
Mounting1U, 19″ rack mount
EnclosureMetal, front LCD, rear connections
Standard Supply
1ORNATE 7000 TSDRNT GPS NTP / PTP Time Server, 1U 19″
2Active GNSS timing antenna with mounting accessories
3RG-6 antenna cable, 50 m, with lightning arrester
4BiharCom Management Server software
5User manual

⬇ Download full brochure (PDF, 4 pages)

Product development is a continuous process — specifications are subject to change without notice.

Talk to Our Team

Get output-configuration and integration guidance for deploying the ORNATE 7000 TSDRNT at your site — antenna placement, port addressing and PTP profiles.

⬇ Download Brochure (PDF) Talk to Our Team →