Products / NTP Time Servers / ORNATE 7000 TSDRNT
ORNATE 7000 TSDRNT GPS NTP / PTP Time Server
Stratum 1 network time from GPS, NavIC, Galileo, BeiDou and GLONASS — over three independent NTP ports and a PTP grandmaster port.
Stratum 1 Time for Every Network on Site
The ORNATE 7000 TSDRNT is a Stratum 1 network time reference for power, process, IT, telecom and railway installations. It takes time from GNSS satellites (GPS, NavIC, Galileo, BeiDou and GLONASS) and distributes it over three independent NTP/SNTP ports, a dedicated PTP (IEEE 1588) grandmaster port, 1PPS, RS-232, RS-485 and four programmable potential-free contacts.
Each NTP port has its own IP address, so one unit can serve three separate networks — for example SCADA, office LAN and CCTV — with no routing between them. A 16 × 2 backlit LCD shows date, time and synchronisation status at a glance, and a GPS-fail alarm contact reports loss of reference.
One Time Source, Every Network
Three NTP Ports + PTP Grandmaster
Three independent NTP/SNTP Ethernet ports (NTP v3/v4, RFC 5905), served in parallel, each with its own IP, mask and gateway — for Windows and Linux servers, IEDs, PLCs, NVRs and switches. A fourth, dedicated PTP port acts as an IEEE 1588 grandmaster with hardware time-stamping.
Dual-Band, Multi-Constellation GNSS
L1 + L5 reception from GPS, NavIC, Galileo, BeiDou, GLONASS and QZSS, with a GNSS receiver timing accuracy of 5 ns (1σ, receiver specification). If GNSS is lost, the server keeps time for a settable holdover period of 1 minute to 24 hours — see our GNSS resilience guide.
Power-Utility PTP Profiles
IEEE 1588-2008 (PTPv2) with the IEC/IEEE 61850-9-3 power utility and IEEE C37.238-2017 power profiles, plus default E2E and P2P. Layer 2 or UDP/IPv4, multicast and unicast (up to 32 slaves) — for substation automation and numerical relays.
Serial, 1PPS & Contact Outputs
- 1PPS, TTL level on BNC
- RS-232 and isolated RS-485: NMEA ZDA, NGTS, T-Format
- 4 programmable potential-free contacts: PPS, PP5S, PPM, PPQH, PPHH, PPH, PPD
- Fail-safe GPS-fail alarm contact
Secure by Design
Password-protected web configuration with login lock-out and session time-out. Management commands are signed with HMAC-SHA256, so the password never travels on the network, and NTP control/monitor queries are disabled. It never serves untraceable time: outputs are held when the unit is not synchronised.
Easy Setup & Central Management
Configure from any web browser, or manage every unit from our Management Server Software → — live status, history, events and settings. Alarms and events go to two SYSLOG servers.
Where the TSDRNT Is Used
Power & Process
Substation automation (IEC 61850) and numerical relays; event loggers and disturbance recorders; SCADA, DCS and EMS servers.
Telecom, Railway & Control Rooms
Telecom, railway and control-room networks, and slave display clocks (wired and RF).
IT & Security
Data centres, CCTV / NVR and IT servers — see NTP for data centres.
Technical Specifications
| GNSS Receiver | |
|---|---|
| Constellations | GPS, NavIC (IRNSS), Galileo, BeiDou, GLONASS, QZSS |
| Frequency bands | L1 / E1 / B1 and L5 / E5a / B2a (dual-band) |
| Channels | 184 |
| Receiver timing accuracy | 5 ns (1σ), GNSS receiver specification |
| Time reference | UTC from GNSS, disciplined system clock (1PPS-locked) |
| Holdover | Keeps serving time after loss of GNSS for a settable period (1 min – 24 h, default 4 h), then reports “not synchronised” |
| Antenna | |
| Type | Active multi-band GNSS timing antenna, outdoor |
| Antenna cable | RG-6, 50 m standard (other lengths on request) |
| Protection | Weather-proof radome; lightning arrester supplied |
| Mounting | Pole / wall mount with fixing accessories |
| NTP Ports (LAN) | |
| Ports | 3 × RJ45, 10/100 Mbps, auto-negotiation |
| Addressing | Independent static IP, mask and gateway per port |
| Protocol | NTP v3 / v4 (RFC 5905), SNTP; UDP / IPv4 |
| Mode | Server (unicast client / server) |
| Stratum | 1 when synchronised; 16 with alarm flag (LI = 3) when not |
| PTP Port | |
| Port | 1 × RJ45, 10/100 Mbps, hardware time-stamping |
| Standard | IEEE 1588-2008 (PTPv2), grandmaster, two-step |
| Profiles | Default E2E and P2P; IEC/IEEE 61850-9-3 (power utility); IEEE C37.238-2017 (power, with TLV); custom |
| Transport | Ethernet Layer 2 or UDP / IPv4 (own IP) |
| Delay mechanism | End-to-end (E2E) or peer-to-peer (P2P) |
| Messaging | Multicast, unicast (negotiated, up to 32 slaves) or both; hybrid unicast Delay_Resp |
| Message rates | Sync up to 16 / s; Announce up to 8 / s |
| Domain / priority | Domain 0 – 127 or 254; Priority 1 / 2 settable |
| Time-scale | PTP (TAI) with UTC offset and leap flags from GNSS, or ARB |
| Best master | Steps aside automatically if a better grandmaster appears |
| Time Signal Outputs | |
| 1PPS output | 1 pulse per second, rising edge on time; TTL level (5 V open circuit, ≈ 2.5 V into 50 Ω); BNC; 100 ms pulse width; suppressed when not synchronised |
| Serial outputs | 1 × RS-232 (DB9) and 1 × isolated RS-485; NMEA ZDA, NGTS, T-Format (selectable per port); 1200 – 115200 baud, 8-N-1 |
| Potential-free contacts | 4 × programmable, solid-state, normally open; modes PPS, PP5S, PPM, PPQH, PPHH, PPH, PPD (time of day settable); pulse width 10 ms – 10 s; UTC or IST time base; normal or inverted; 125 V DC / 88 V AC rms, 75 mA |
| Alarm contact | 1 × GPS-fail potential-free changeover contact (NO / COM / NC), 30 V DC, 1 A (SELV); fail-safe — drops out on fault or power loss; optional alarm while in holdover |
| Display, Indication & Configuration | |
| Display | 2 × 16 character backlit LCD |
| Status LEDs | Power, System OK; link / activity on every Ethernet port |
| Displayed data | Date and UTC time; synchronisation state, GNSS and 1PPS status; port IP address and NTP request count; unit ID |
| Configuration | Web browser (HTTP), password protected; BiharCom Management Server software (Windows) |
| Settings storage | Non-volatile memory; restore defaults from the management software |
| Network Protocols & Management | |
| Time protocols | NTP v3 / v4 (RFC 5905) server, SNTP clients; PTPv2 – IEEE 1588-2008 grandmaster (multi-profile) |
| Networking | IPv4, UDP, TCP, ARP, ICMP (ping), IGMPv2 (PTP port) |
| SYSLOG | RFC 5424, two configurable servers; selectable facility, severity and event groups (sync, GNSS, alarm, network, PTP, outputs, system, configuration, security) |
| Central management | Auto-discovery of units, live status, clock history, event log, remote configuration, save and reboot |
| Network Security | |
| Web access | User name and password; 5 failed logins lock access for 60 s; 15 min session time-out |
| Management commands | HMAC-SHA256 signed with one-time challenge (replay-protected); password never sent over the network |
| NTP hardening | Control (mode 6) and private (mode 7) queries disabled — no amplification risk |
| Audit | Logins, failures and configuration changes reported to SYSLOG |
| Synchronisation Integrity | |
| Not synchronised | NTP stratum 16 with alarm flag; PTP clock class “not traceable”; 1PPS and serial time withheld |
| Holdover | Keeps serving time for the set holdover period; optional alarm while in holdover |
| Self-recovery | Watchdog supervision; a stalled network port is reset on its own without disturbing the others |
| Status reporting | LCD, alarm contact, web page, management software and SYSLOG |
| Power, Environment & Mechanical | |
| Power input | 90 – 264 V AC, 47 – 63 Hz / 127 – 370 V DC |
| Consumption | < 15 W |
| Operating temperature | 0 to +50 °C |
| Storage temperature | −20 to +70 °C |
| Humidity | Up to 90 % RH, non-condensing |
| Mounting | 1U, 19″ rack mount |
| Enclosure | Metal, front LCD, rear connections |
| Standard Supply | |
| 1 | ORNATE 7000 TSDRNT GPS NTP / PTP Time Server, 1U 19″ |
| 2 | Active GNSS timing antenna with mounting accessories |
| 3 | RG-6 antenna cable, 50 m, with lightning arrester |
| 4 | BiharCom Management Server software |
| 5 | User manual |
⬇ Download full brochure (PDF, 4 pages)
Product development is a continuous process — specifications are subject to change without notice.